太原高低壓配電柜的安全操作步驟是什么?山西(xi)景泰電(dian)(dian)(dian)氣(qi)多年來致力于生產(chan)各種規格(ge)(ge)的山西(xi)配(pei)電(dian)(dian)(dian)柜(ju),太(tai)(tai)原(yuan)(yuan)配(pei)電(dian)(dian)(dian)箱(xiang),自動化控制柜(ju),山西(xi)箱(xiang)式變電(dian)(dian)(dian)站(zhan),高低壓(ya)(ya)開關柜(ju),太(tai)(tai)原(yuan)(yuan)低壓(ya)(ya)配(pei)電(dian)(dian)(dian)柜(ju),山西(xi)高壓(ya)(ya)成套(tao)配(pei)電(dian)(dian)(dian)柜(ju),配(pei)電(dian)(dian)(dian)工程;要問太(tai)(tai)原(yuan)(yuan)成套(tao)配(pei)電(dian)(dian)(dian)柜(ju)價(jia)格(ge)(ge),低壓(ya)(ya)配(pei)電(dian)(dian)(dian)柜(ju)廠家,配(pei)電(dian)(dian)(dian)箱(xiang)哪家好(hao);歡迎來到本公司(si);主營區域:山西(xi),太(tai)(tai)原(yuan)(yuan),運城,忻州,大同,晉中,長治,朔州,臨汾,榆次,晉城,呂梁,陽泉.
高(gao)低(di)壓配電柜的操(cao)作安(an)全是(shi)第(di)1位,而進(jin)行(xing)操(cao)作時應(ying)按(an)照安(an)全規程進(jin)行(xing)操(cao)作。
1、在全部和部分帶電的盤上進行工作,應將檢修(xiu)設備與運行設備以明顯標志(zhi)隔開。
2、有電流互感器和(he)電壓互感器的二(er)次繞(rao)組應有永(yong)性的、可靠的保(bao)護接地。
3、在運行的電流互感(gan)器二(er)次回路(lu)上工作時,應采取下(xia)列安全措(cuo)施(shi):
3.1嚴禁將電流(liu)回路斷開(kai)。
3.2為了(le)可靠地將電流(liu)互感器二次線(xian)圈短路,必須使(shi)用短路片和短路線(xian),禁止使(shi)用導(dao)線(xian)纏繞。
3.3禁止在(zai)電(dian)流互感器與短路端子之間的回路和導(dao)線上進行工作(zuo)。
4、在運(yun)行中的電壓(ya)互感器二次回路(lu)上工(gong)作時,應采取下(xia)列(lie)安全措(cuo)施:
4.1嚴(yan)格防止短路或接(jie)地
4.2應使用絕緣工具(ju)、戴絕緣手(shou)套,必要時在工作前停用有關(guan)繼電保(bao)護裝置。
4.3接(jie)臨時(shi)負載(zai)時(shi),必須裝有的開關和熔斷器(qi)。
4.4二(er)次(ci)回路通(tong)電試(shi)驗時,為(wei)防止(zhi)由二(er)次(ci)側(ce)向一次(ci)反變(bian)壓(ya),除(chu)將二(er)次(ci)回路斷開外,還應取下一次(ci)熔斷器。
4.5二次回(hui)路通(tong)電或耐壓(ya)試驗前,應通(tong)知(zhi)值班員和有關(guan)人員,并派人看守現(xian)場,檢(jian)查(cha)回(hui)路,確認無人工作后方(fang)可加壓(ya)。
4.6 檢查斷電(dian)保護和二次 回路的工作人員(yuan),未(wei)經值班人員(yuan)許可,不準進行倒閘操作。
以上內容由山西景泰電氣為您整理發布,更多關于山西高(gao)壓配電(dian)柜(ju)的資訊,請致電咨詢!